Bitumen Asphaltive · Middle East Supply Desk

Penetration grade · EN 12591

Bitumen 40/60: EN 12591 Specification, Applications and Export Supply

Bitumen 40/60 is the general highway paving grade of warm-climate European practice, with a penetration band of 40 to 60 tenths of a millimetre and a ring and ball softening point band of 48 to 56 °C. It also occupies the most awkward commercial position on the whole EN 12591 ladder, because it overlaps both of its neighbours completely. A batch measuring 45 ×0.1 mm satisfies 35/50 and 40/60 at once; a batch measuring 55 satisfies 40/60 and 50/70 at once; and there is no penetration value inside the 40/60 band that does not also belong to one of those two grades. That is deliberate in the European system, and it carries a consequence a buyer has to act on: the same cargo can legitimately be offered against more than one grade name, so the grade name alone does not identify what you are getting. Only the certificate does, and only when it is read against the grade written into your own purchase order.

40–60Penetration, ×0.1 mm
48–56 °CSoftening point, EN 1427
≥ 50 %Retained penetration, RTFOT
≤ -7 °CFraass breaking point, EN 12593

Definition

What Bitumen 40/60 actually is

Bitumen 40/60 is a paving grade bitumen defined by EN 12591, the European standard for paving grade bitumens, whose needle penetration at 25 °C falls between 40 and 60 tenths of a millimetre and whose ring and ball softening point falls between 48 and 56 °C.

As with every penetration grade, the name is a measurement rather than a brand or a quality claim. A sample is conditioned to 25 °C, a standard needle carrying a 100 g load is released into it for five seconds, and the depth the needle reaches is read off in tenths of a millimetre. Any result from 40 to 60 makes the material a 40/60. The procedure is EN 1426, which is technically equivalent to ASTM D5 and IS 1203. European practice writes the unit as ×0.1 mm where American practice writes dmm; it is the same quantity under a different house style, and nothing turns on which appears on the certificate.

Penetration and hardness run in opposite directions, so a lower number means a stiffer binder. On the EN 12591 ladder 40/60 sits one rung harder than 50/70, the mainstream European paving grade, and one rung softer than 35/50. Its softening point band of 48 to 56 °C sits two degrees above 50/70 at both ends and two degrees below 35/50 at both ends. That is the whole of its technical character stated in one line: a general highway paving binder for climates warm enough that the mainstream grade is beginning to look soft, but not so demanding that a heavy-duty wearing course grade is called for.

The commercial problem, stated at the top

Everything else on this page follows from a single arithmetic fact, so it belongs here rather than three sections down. The 40/60 band runs from 40 to 60. The band below it, 35/50, runs from 35 to 50. The band above it, 50/70, runs from 50 to 70. Intersect them and the result is uncomfortable: every penetration value inside the 40/60 band also belongs to 35/50 or to 50/70. Values from 40 to 50 are shared with 35/50, values from 50 to 60 are shared with 50/70, and the single value 50 belongs to all three grades at once. There is no penetration result a laboratory can report that identifies a binder as a 40/60 and nothing else.

The softening point band behaves the same way. 40/60 requires 48 to 56 °C. 50/70 requires 46 to 54 °C, so 48 to 54 is shared with it. 35/50 requires 50 to 58 °C, so 50 to 56 is shared with that. Union those two windows and you have 48 to 56 °C, which is the entire 40/60 band. Again, nothing is left over.

So the two properties that appear at the top of every Certificate of Analysis, the two a buyer checks first and the two that most people believe define a penetration grade, cannot on their own establish that a cargo is a 40/60. They can only establish that it is not disqualified from being one. This is not a drafting error and it is not a loophole. It is how the European system is built, and the section headed One cargo, three grade names sets out what it means for a purchase order, a certificate and a dispute.

What the grade is for

The engineering case for stepping up from 50/70 to 40/60 is modest and specific. Permanent deformation, which is to say rutting, is driven by the binder losing stiffness as the pavement warms and by traffic loading the same wheel path repeatedly. Moving from 50/70 to 40/60 raises the softening point window by two degrees at both ends and raises the floor under the aged softening point by two degrees with it. That is a real gain in high-temperature stiffness and it is bought without moving far from the mainstream grade, which matters because plant, laying practice and mix designs across most European and Mediterranean markets are built around 50/70 and its close neighbours.

The cost is paid at the other end of the temperature scale. EN 12591 places the Fraass breaking point limit for 40/60 at a maximum of -7 °C against -8 °C for 50/70, -10 °C for 70/100 and -12 °C for 100/150. The harder grade is permitted to become brittle at a warmer temperature, which is the standard’s own way of saying that stiffness is bought with cracking resistance. Where the winter is genuinely cold, that trade is a bad one, and the section on where 40/60 is the wrong choice sets out exactly why.

What EN 12591 controls that an ASTM data sheet does not

A buyer used to reading Gulf and South Asian export data sheets should understand that the difference between an EN order and an ASTM order is less a difference in the binder than a difference in what the producer is obliged to prove. EN 12591 asks for four things an ASTM-based export data sheet usually does not carry:

  • A two-sided softening point band for every grade. Determined by EN 1427, and for 40/60 the band is 48 to 56 °C. ASTM D946 sets no softening point requirement whatsoever, for any of its grades. Softening point figures printed on export data sheets for ASTM paving grades are refinery and trading practice, not requirements of that standard.
  • Ageing by RTFOT, not TFOT. Resistance to hardening is assessed by the rolling thin-film oven test to EN 12607-1, and three separate limits are placed on the residue: change of mass, retained penetration and softening point after hardening.
  • A Fraass breaking point. EN 12593 measures the temperature at which a thin film of binder cracks when it is cooled and flexed. There is no counterpart anywhere in ASTM D946. Note how EN 12591 handles it: the Fraass limit sits in the group of properties whose requirements are applied according to national circumstances and climate rather than in the group demanded of every grade in every country, which is exactly why it has to be named in the order.
  • Solubility in toluene. EN 12592 uses toluene where ASTM D2042 uses trichloroethylene. The limit is the same 99.0 %, but the solvent is not, so a laboratory reporting solubility in trichloroethylene has not run the European method.

All four are checkable on a Certificate of Analysis before a cargo moves. If a supplier offers 40/60 and the certificate carries only penetration, softening point, ductility and trichloroethylene solubility, that document is not evidence of EN 12591 conformity. It is an ASTM-style data sheet with a European grade name typed at the top.

Ageing, and what the three RTFOT limits mean in numbers

The ageing requirement deserves attention on its own terms, because it is the part of the EN specification that most directly predicts how the pavement behaves after the mixing plant, and because on this grade it is one of only two lines that separate 40/60 from the grades either side of it.

The rolling thin-film oven test to EN 12607-1 ages a continuously renewed film of binder inside rotating glass bottles with an air jet, at 163 °C. EN 12591 then places three limits on what comes out. Change of mass for 40/60 is capped at ± 0.5 %, and the plus-or-minus is not decorative: a binder can gain mass through oxidation as well as lose it through volatilisation, and a certificate reporting only a loss figure has answered half the question. Retained penetration must be at least 50 % of the original value, so a cargo entering the test at 52 ×0.1 mm must still measure at least 26 afterwards, and a cargo entering at the bottom of the band, 40, must still measure at least 20. Softening point after hardening must be at least 50 °C, which puts a floor under the aged binder’s high-temperature stiffness.

Compare that last figure with the neighbours and a pattern appears. The aged softening point floor is 52 °C for 35/50, 50 °C for 40/60 and 48 °C for 50/70. Across the ladder the floor tracks two degrees above the bottom of each grade’s fresh softening point band, which is a compact way of saying that the standard expects a harder grade to still be a harder grade after the mixer has had its way with it. On this page that line matters more than anywhere else on the ladder, because it is the only EN 12591 requirement whose value is different for all three of 35/50, 40/60 and 50/70. Retained penetration does not separate 40/60 from 50/70 at all: both are set at 50 %.

The one thing to settle before reading any 40/60 certificate

EN penetration bands are deliberately wide and adjacent bands deliberately overlap, and around 40/60 the overlap is total. A binder measuring 46 ×0.1 mm with a softening point of 53 °C is inside 35/50 and inside 40/60 at the same time, on both lines. Move the penetration to 56 and the same is true of 40/60 and 50/70. Nothing on that certificate says which grade the material is, because on those two lines it is two grades. Which grade it can be sold as depends on the ageing residue, on the low-temperature limit where it is called up, on what the producer actually tested against, and above all on what the contract named. Read every 40/60 certificate against the grade written in your own purchase order rather than against whichever grade heading the producer printed on the page.

Technical data

Bitumen 40/60 specification table (EN 12591)

These are the requirements EN 12591 places on grade 40/60, with the European test method that produces each value. This is the table a European engineer will hold your Certificate of Analysis against, line by line.

Typical export specification for Bitumen 40/60, following the requirements of EN 12591.
Property Test method Unit Min Max
Penetration at 25 °C, 100 g, 5 s EN 1426 (ASTM D5) ×0.1 mm 40 60
Softening point, ring & ball EN 1427 (ASTM D36) °C 48 56
Flash point, Cleveland open cup EN ISO 2592 (ASTM D92) °C 230
Solubility in toluene EN 12592 wt % 99.0
Change of mass after RTFOT EN 12607-1 wt % ± 0.5
Retained penetration after RTFOT EN 1426 on EN 12607-1 residue % of original 50
Softening point after RTFOT EN 1427 on EN 12607-1 residue °C 50
Fraass breaking point EN 12593 °C -7
These are the properties EN 12591 governs for grade 40/60. They are quoted here for technical orientation and are not a contractual guarantee: the binding values for any shipment are the ones written into the sales contract and evidenced by the batch Certificate of Analysis. Three qualifications belong with the table. First, the Fraass line sits in the group of EN 12591 properties whose requirements are applied according to national circumstances and climate rather than demanded of every cargo everywhere, so it is a contractual requirement where the destination specification calls it up and an optional extra where it does not. Say at the enquiry stage that you need the test run, because it cannot be added to a certificate afterwards. Second, that same national-circumstances group also contains a maximum increase in softening point after hardening, a minimum kinematic viscosity at 135 °C by EN 12595, a dynamic viscosity at 60 °C by EN 12596, and a wax content cap by EN 12606-1. Those limits are grade-specific and are not reproduced here; take them from the current edition of EN 12591 and the national annex that applies to your project. Third, the flash point floor in EN 12591 moves with the band rather than being one figure for the whole standard, so read the 230 °C above as the requirement for this grade and check which floor applies to any other band you are comparing against. Note also what the standard does not require: ductility, water content and density are absent from the requirement list, although producer data sheets normally report density anyway (typically 1.01–1.06 g/cm³ at 25 °C by EN 15326 or ASTM D70) because converting invoiced tonnes into tank volume depends on it. The methods behind each line are set out in the bitumen test methods reference.

The spine of this page

One cargo, three grade names: what the 40/60 overlap does to a purchase

40/60 is the grade with no territory of its own. Every penetration value it contains is also contained by 35/50 or by 50/70, and the same is true of its softening point band. That makes the grade name on an offer a weaker piece of information than almost any buyer assumes, and it changes what a purchase order and an inspection scope have to say.

Start with the arithmetic, because the arithmetic is the argument

Take the three bands exactly as EN 12591 publishes them and intersect them.

  • Penetration. 35/50 covers 35 to 50, 40/60 covers 40 to 60, 50/70 covers 50 to 70. The window 40 to 50 ×0.1 mm belongs to 35/50 and 40/60. The window 50 to 60 belongs to 40/60 and 50/70. The single value 50 belongs to all three. Add the two windows together and you have 40 to 60, which is the whole of the 40/60 band. Nothing is left over.
  • Softening point. 35/50 requires 50 to 58 °C, 40/60 requires 48 to 56 °C, 50/70 requires 46 to 54 °C. The window 50 to 56 °C is shared with 35/50 and the window 48 to 54 °C is shared with 50/70. Together they cover 48 to 56 °C, which is again the whole of the 40/60 band.

The conclusion is blunt and it is worth stating without softening it. There is no combination of penetration and softening point that makes a binder a 40/60 and not also something else. A cargo at 44 and 53 is a 35/50 as well. A cargo at 56 and 49 is a 50/70 as well. A cargo at 50 and 52 is all three grades simultaneously. On the two properties that define a penetration grade in most people’s minds, 40/60 has no exclusive identity at all.

Compare that with the ends of the ladder, where the picture is entirely different. 20/30 touches 30/45 at the single value 30 and shares nothing else with anything. 100/150 and 160/220 do not meet at all, and neither do 160/220 and 250/330, so there are penetration values, 155 ×0.1 mm for instance, that no EN 12591 grade contains. The bands are not uniformly wide or uniformly overlapping. They are crowded in the middle and sparse at the extremes, and 40/60 sits at the most crowded point of all.

Where the three grades actually separate

They separate on the lines a buyer tends to skim: the ageing residue and, where a national annex calls it up, the low-temperature limit. Those are set per grade and they move as the grade name changes.

  • Softening point after hardening (EN 1427 on the EN 12607-1 residue). Minimum 52 °C for 35/50, 50 °C for 40/60, 48 °C for 50/70. This is the only EN 12591 requirement whose value is different for all three grades, which makes it the single most informative line on a certificate in this part of the ladder.
  • Retained penetration after RTFOT. Minimum 53 % for 35/50, 50 % for 40/60 and 50 % for 50/70. Note carefully what this line does and does not do. It separates 35/50 from the other two, and it does not separate 40/60 from 50/70 at all.
  • Fraass breaking point (EN 12593), where the national annex calls it up. Maximum -5 °C for 35/50, -7 °C for 40/60 and -8 °C for 50/70. This line runs the opposite way to the ageing lines: naming the softer grade tightens the brittleness limit, naming the harder grade relaxes it.

Everything else, on this cluster, is identical. Solubility is minimum 99.0 % in toluene for all three. Change of mass after RTFOT is a maximum of ± 0.5 % for all three. A result on either line can disqualify a cargo, but it can never identify which of the three grades that cargo is. And because no grade in the cluster is simply stricter than the others on every line, the choice cannot be made by picking the hardest name available and assuming it covers you.

A worked example

Consider a batch with these measured values: penetration 47 ×0.1 mm, softening point 52 °C, retained penetration after RTFOT 51 %, softening point after hardening 51 °C, Fraass breaking point -7 °C.

  • Against 40/60: penetration inside 40 to 60, softening point inside 48 to 56, retained penetration above the 50 % floor, aged softening point above the 50 °C floor, Fraass at the -7 °C ceiling and therefore compliant. It passes every line.
  • Against 35/50: penetration and softening point both pass, and comfortably. But retained penetration of 51 % is below the 53 % floor that 35/50 requires, and the aged softening point of 51 °C is below the 52 °C floor. It fails twice, on lines that appear near the bottom of the certificate.
  • Against 50/70: softening point and both ageing lines pass, but the penetration of 47 is below the 50 floor of that band, so it fails on the very first line. Where the Fraass test is called up it fails a second time, and in a direction buyers routinely get backwards: -7 °C does not meet the maximum of -8 °C that 50/70 carries. The low-temperature limit tightens as the grade softens, so the softer neighbour is the harder one to satisfy on that line.

That batch is a 40/60 and nothing else. Now move it slightly. Take penetration 52, softening point 51, retained penetration 54 %, aged softening point 53 °C, Fraass -8 °C. That material passes 40/60 and it passes 50/70 outright, and it fails 35/50 only on penetration. One certificate, two grade names, both honestly claimed. That is the position a 40/60 buyer is actually in, and it is why the rest of this section is about paperwork rather than about chemistry.

What follows for the buyer

1. The grade named in the contract is a commercial decision as much as a technical one. Where a producer holds material that satisfies 40/60 and 50/70 alike, nothing physical changes by writing one name rather than the other. What changes is the limit table the cargo will be judged against, the tests the producer has to run and be prepared to defend, and the argument available to each side if a result at destination lands near an edge. Name the grade your specification requires, and understand that the name is doing work the material is not.

2. A certificate must be read against the grade you named, not the grade it is headed with. This is the practical failure mode and it is a quiet one. A producer with a batch at 52 ×0.1 mm may head the certificate 50/70 because that is what the previous customer bought, and offer it against your 40/60 order on the basis that penetration and softening point both fall inside your bands. They may well do. But if the batch was produced and released against the 50/70 limit table, the aged softening point may have been accepted at 49 °C, which is compliant for 50/70 and below the 50 °C floor for 40/60, and nobody has done anything wrong except hand you a certificate written for a different grade. The same trap works in the other direction with a 35/50 heading: that grade’s ageing floors are higher than yours, so the certificate will pass your check, but its Fraass limit is -5 °C where yours is -7 °C, and a cargo released against the 35/50 low-temperature limit does not automatically meet the 40/60 one.

3. Band edges are softer than they look. EN 1426 and EN 1427 both publish precision statements giving the spread expected between two results in one laboratory and between two laboratories. A batch whose true penetration is 40 sits exactly on the bottom edge of the 40/60 band; a re-test at destination reporting 39 puts it outside the grade with neither laboratory being wrong. The same applies at 60. Any grade claim resting on a value at the very edge of a band is fragile for that reason alone. Where a cargo is likely to test near an edge, name ASTM D3244 or an equivalent agreed practice in the contract for combining a supplier result and a receiver result into an assigned test value, which converts a future stand-off into a calculation.

4. Twenty units is a wide band, and the mix design has to survive it. This is the point most specific to 40/60 and the one least often raised at enquiry stage. The band is twenty penetration units wide, which is half the value of its own lower edge. Two cargoes can both be fully compliant 40/60 and differ by more than the entire width of the ASTM 40-50 band. A plant that closed its mix design on a binder at 42 ×0.1 mm and then receives a compliant cargo at 58 is working with a materially different material: different mixing and compaction viscosity, different stiffness in the finished mat, different deformation behaviour in the first hot summer. If your mix design depends on landing in one part of the band, do not rely on the grade name to deliver it. Buy 40/60 to EN 12591 and add a narrower penetration band as an additional contractual limit inside the grade, in the form penetration at 25 °C by EN 1426, 45 to 55 ×0.1 mm, as an additional contractual limit within the EN 12591 40/60 grade. That keeps the whole EN limit table underneath the order, is enforceable because every term in it is defined, and honestly narrows the field of available cargoes, which will show in price and in lead time. Those are the consequences of a tighter requirement, not reasons to avoid stating it.

5. Do not accept the word equivalent in place of a grade name. The clause 40/60 or equivalent has no test attached to it and no agreed meaning, and in a cluster this crowded both parties will read it in their own favour on the day it matters. If a substitution to 35/50 or 50/70 is genuinely acceptable to the engineer, have it approved in writing, by name, with the standard and the edition cited, before production. The wider cross-system picture is set out on the grade equivalence reference.

Which of the three a specification writer should actually name

Set the commercial question aside and the engineering distinction between the three is real, even though the bands overlap. 35/50 is the heavy-duty grade: wearing and binder courses where slow, channelised or very heavy traffic on a warm pavement makes rutting the governing risk. 50/70 is the mainstream European paving grade, the default answer for a temperate climate and ordinary highway loading. 40/60 is the step between them, and it is the right name when the climate is warm enough that the mainstream grade is being pushed but the pavement is not being punished. Where the design traffic, the layer and the climate point clearly at one of those three descriptions, name that grade. Where they point between two of them, the overlap is not a problem to be solved. It is the standard saying that either name will be served by the same material, and that the choice can be made on availability and on which limit table you would rather be holding when the cargo is tested at destination.

The EN ladder

Where 40/60 sits, and which bands it overlaps

EN 12591 defines a ladder of nine paving grades running from very hard to very soft, and the bands in the middle of that ladder are wide enough to run into each other. The fourth column is the one worth studying: it names, for each grade, the penetration range it shares with a neighbour.

Paving grades under EN 12591 with penetration and softening point bands, and the penetration overlap each grade has with its neighbours.
EN 12591 grade Penetration at 25 °C (×0.1 mm) Softening point, R&B (°C) Penetration shared with neighbouring grades Typical use
20/30 20–30 55–63 Touches 30/45 at the single value 30 and nowhere else High-modulus asphalt, very heavily loaded base
30/45 30–45 52–60 Shares 35–45 with 35/50 and 40–45 with 40/60 Heavy-duty binder and base courses
35/50 35–50 50–58 Shares 35–45 with 30/45, 40–50 with 40/60, and touches 50/70 at 50 Heavy traffic wearing and binder courses
40/60 40–60 48–56 Shares 40–45 with 30/45, 40–50 with 35/50 and 50–60 with 50/70 — the whole band is shared General highway paving in warm climates — the grade on this page
50/70 50–70 46–54 Shares 50–60 with 40/60 and touches 70/100 at 70 The mainstream European paving grade
70/100 70–100 43–51 Touches 50/70 at 70 and 100/150 at 100 Cooler regions, thin surfacings, surface dressing
100/150 100–150 39–47 Touches 70/100 at 100; no overlap at all with 160/220 Cold climates, surface dressing, grouted macadam
160/220 160–220 35–43 None — the ladder leaves a gap between 150 and 160 Very cold climates, specialised low-stiffness mixes
250/330 250–330 30–38 None — a further gap sits between 220 and 250 Cold-climate spray sealing and specialised low-stiffness work
Two patterns in that fourth column decide how a 40/60 purchase behaves. At the hard and soft ends of the ladder the grades barely meet: 20/30 touches 30/45 at one value, and 100/150, 160/220 and 250/330 do not meet each other at all, so there are penetration values that no EN 12591 grade contains. In the middle the bands pile up, and 40/60 is where they pile up hardest. Its lower half is shared with 35/50, its upper half is shared with 50/70, its bottom five units are shared with 30/45 as well, and the value 50 belongs to three grades at once. Nothing in the band belongs to 40/60 alone. That is not an error of drafting. European practice accepts that one binder can legitimately serve more than one application and puts the work of separating the grades onto the softening point band and the ageing limits rather than onto the penetration number. The practical consequence is that ordering by penetration alone is not ordering to EN 12591. Read the two band columns as attributions rather than as verifications, and that applies to every row in the table rather than to any one grade: the penetration and softening point bands quoted here are the bands the site’s grade equivalence reference publishes, they are not values independently verified here against the standard text, and the contractual limit for any of these grades must be taken from the edition of EN 12591 the contract cites together with any applicable national annex.

Side by side

40/60 against its two EN neighbours, requirement by requirement

Every line EN 12591 sets for the three overlapping grades, in one place. The rows where the three columns are identical are the rows that cannot decide a grade; the rows where they differ are the rows that can. On this cluster there are only three of the latter, and one of them separates 40/60 from only one of its neighbours.

EN 12591 requirements for grades 35/50, 40/60 and 50/70 compared line by line.
Requirement and method 35/50 40/60 50/70 What the difference does
Penetration at 25 °C, EN 1426 (×0.1 mm) 35–50 40–60 50–70 40–50 is shared with 35/50 and 50–60 with 50/70, so no penetration result identifies a 40/60 on its own
Softening point, ring & ball, EN 1427 (°C) 50–58 48–56 46–54 48–54 is shared with 50/70 and 50–56 with 35/50, so this line cannot identify the grade either
Solubility in toluene, EN 12592 (wt %) min 99.0 min 99.0 min 99.0 Identical. Confirms the material is genuine bitumen, not which grade it is
Change of mass after RTFOT, EN 12607-1 (wt %) max ± 0.5 max ± 0.5 max ± 0.5 Identical across the cluster. Note the plus-or-minus: a certificate reporting loss only has answered half the question
Retained penetration after RTFOT (% of original) min 53 min 50 min 50 Separates 35/50 from the other two and does nothing at all to separate 40/60 from 50/70
Softening point after hardening, EN 1427 on RTFOT residue (°C) min 52 min 50 min 48 The only requirement in the cluster whose value differs for all three grades. A batch aged to 49 °C is a 50/70 and is not a 40/60, whatever its fresh penetration says
Fraass breaking point, EN 12593 (°C) max -5 max -7 max -8 Runs the opposite way to the ageing lines: the softer the grade, the harder the brittleness limit. Applied according to national circumstances, so confirm against the current edition and the national annex
Penetration window shared with 40/60 (×0.1 mm) 40–50 50–60 The two shared windows tile the whole 40/60 band with nothing left over
Softening point window shared with 40/60 (°C) 50–56 48–54 The same again on the second headline property. 40/60 has no exclusive softening point territory
Typical role in European practice Heavy traffic wearing and binder courses General highway paving in warm climates The mainstream European paving grade The engineering distinction is real even though the bands overlap. It is the certificate, not the name, that proves which limit table was applied
Read the table downwards rather than across. The top four rows are either overlapping or identical, which means the properties most buyers check first cannot tell these three grades apart in the middle of their ranges. Below them, only three rows do any work, and they do it unevenly: retained penetration marks off 35/50 but leaves 40/60 and 50/70 indistinguishable; the Fraass line is optional unless a national annex or your own contract calls it up; and the aged softening point is the one line that carries a different value for every grade in the cluster. If your purchase order names 40/60, ask for the EN 12607-1 residue results as measured numbers rather than as pass-or-fail statements, and check them against the 50 % and 50 °C floors yourself. That single request does more to protect a 40/60 order than any other clause available to a buyer.

The ASTM question

Does an ASTM 40-50 certificate answer a 40/60 enquiry?

This is the second confusion that lands on this grade, and it is entirely understandable. Both names start with 40, both describe a mid-hard paving binder, and a great deal of export material is certified to ASTM. A buyer holding an ASTM 40-50 certificate will usually assume it answers a 40/60 enquiry. Sometimes it does and sometimes it does not, and the honest answer has to be given property by property.

First, what the two standards actually contain

ASTM D946 names exactly five penetration grades: 40-50, 60-70, 85-100, 120-150 and 200-300. AASHTO M20 names the same five. There is no ASTM 40/60, no ASTM 30/40 and no ASTM 20/30, whatever a data sheet heading may say. EN 12591 names nine: 20/30, 30/45, 35/50, 40/60, 50/70, 70/100, 100/150, 160/220 and 250/330. There is no EN 40-50 and no EN 120/150 or 200/300 either, because those are ASTM designations. A grade name belongs to one standard at a time, and the first question to settle about any offer is which of the two documents the certificate was written against.

That matters here because the two nearest names are so close that the difference disappears in conversation. A trader saying forty fifty and a buyer hearing forty sixty are discussing two grades from two standards with different bands, different property lists and different ageing tests. Write both the grade and the standard into every document and the ambiguity disappears at no cost.

Penetration: yes in one direction, and only in one direction

On penetration alone the arithmetic is favourable and worth stating plainly. The ASTM D946 40-50 band runs from 40 to 50 dmm. The EN 12591 40/60 band runs from 40 to 60 ×0.1 mm, and they are the same unit. The ASTM band therefore sits entirely inside the European one, so every compliant ASTM 40-50 satisfies 40/60 on penetration. If penetration were the only question, an ASTM 40-50 certificate would answer a 40/60 enquiry every time.

Containment runs one way only, and the reverse direction fails badly. A 40/60 measuring anywhere above 50 ×0.1 mm is fully compliant with EN 12591 and outside the ASTM 40-50 band, and that is the whole upper half of the European band: the 40/60 band is twenty units wide and the ten units above 50 are exactly half of it. So a European cargo offered against an ASTM 40-50 specification is a genuine risk, while an ASTM cargo offered against a European penetration band is not. Buyers routinely reason as though the relationship were symmetrical. It is not.

There are two situations in which even the favourable direction fails, and both are worth knowing.

  • The bottom edge. An ASTM 40-50 batch released at exactly 40 dmm sits on the floor of the 40/60 band with no margin at all. Every test method publishes a precision statement, and a destination laboratory reporting 39 on the same material puts the cargo outside 40/60 with neither laboratory being wrong. A 40-50 cargo in the 40 to 42 range is technically inside your grade and practically fragile, which is a different thing from compliant.
  • The document is not what it says. A large share of what circulates as an ASTM 40-50 certificate is an export data sheet headed 40/50 rather than a release against the D946 limit table. That is a commercial document. It may be entirely accurate about the penetration and still carry no evidence about the properties D946 controls, let alone the ones it does not. Read what the document claims to be, not what the grade name suggests.

Softening point: a separate question, and usually the one that fails

ASTM D946 sets no softening point requirement at all. Not a band, not a minimum, not a maximum, for any of its five grades. So a producer supplying compliant ASTM 40-50 has never been obliged to control the softening point of that material and has no reason to have measured it against any limit.

EN 12591 requires 40/60 to sit between 48 and 56 °C by EN 1427. A compliant ASTM 40-50 whose softening point measures 58 °C is a perfectly good 40-50 and a failed 40/60. Nothing improper has occurred. The requirement simply did not exist in the standard the cargo was made to.

Two follow-on points matter more than the general statement. First, many export data sheets for ASTM paving grades do print a softening point range, and buyers read it as though it were a specification limit. It is not. It is refinery or trading practice, and where the contract cites ASTM D946 there is no standard limit behind that figure to enforce. Second, a softening point that has never been controlled tends to drift with crude source and process route, so consistency between shipments is not assured either. If your project needs the EN band, the way to get it is to name EN 1427 and the 48 to 56 °C limits in the contract, not to hope that an ASTM cargo happens to land inside them.

Ageing: a different test, a different residue and numbers that do not compare

This is the third separate question and it is the one most often waved through. EN 12591 assesses hardening by the rolling thin-film oven test to EN 12607-1, which ages a continuously renewed film inside rotating glass bottles with an air jet at 163 °C. ASTM D946 assesses it by the thin-film oven test of ASTM D1754, which ages a static film in a shallow dish at 163 °C for five hours. Both answer the same engineering question and they do not produce the same residue.

The limits then differ in kind as well as in number. For ASTM 40-50 the requirement is retained penetration after TFOT of at least 55 %. For EN 40/60 the requirements are change of mass no more than ± 0.5 %, retained penetration at least 50 % and softening point after hardening at least 50 °C. A buyer glancing at the two percentages will conclude that the American requirement is stricter. That conclusion is not available, because the residues are produced by different tests: 55 % of one thing and 50 % of another are not comparable quantities, and no arithmetic converts between them. More importantly, the aged softening point floor is a requirement with no ASTM counterpart whatsoever, so no D946 certificate can evidence it, however complete that certificate is. If your order needs that line, it has to be arranged before production.

The rest of the certificate

  • Low-temperature behaviour. ASTM D946 has no low-temperature requirement of any kind. The Fraass breaking point by EN 12593, with its maximum of -7 °C for 40/60, exists only if somebody ordered the test. It is the line most often absent when an ASTM-supplied cargo is offered against a European specification.
  • Solubility. Both standards set a minimum of 99.0 %, but EN 12592 determines it in toluene and ASTM D2042 in trichloroethylene. A genuine paving bitumen passes both. The point is documentary: if the contract says EN 12592 and the certificate says trichloroethylene, the laboratory has run a different method.
  • Flash point. EN 12591 requires a minimum of 230 °C for 40/60 by EN ISO 2592, Cleveland open cup. ASTM D946 requires a minimum of 232 °C by ASTM D92, and many export data sheets state a minimum of 250 °C. This is one of the few places where the ASTM requirement and the commercial data sheet sit above the European standard, so it rarely causes a rejection.
  • Ductility. ASTM D946 requires a minimum of 100 cm at 25 °C by ASTM D113. EN 12591 does not require ductility at all, so a compliant European certificate may legitimately omit it. Ask for it explicitly if your own project document calls it up.

What to check, in order

Given an ASTM 40-50 certificate and a 40/60 enquiry, four checks settle it, and they take minutes.

  1. Which standard is the document written against? A release against ASTM D946 and an export data sheet headed 40/50 are different animals. Find the standard reference and the batch identity.
  2. Where in the band does the penetration sit? Inside 40 to 50 it satisfies the 40/60 band. Below about 42 it is fragile at the lower edge, and that fragility is yours to carry once the cargo is afloat.
  3. Is there a softening point, and against what? If there is no figure, the EN band is unevidenced. If there is a figure, confirm it was measured by EN 1427 or ASTM D36 and check it against 48 to 56 °C. Remember that any range printed on the data sheet is practice, not an ASTM requirement.
  4. Which ageing test was run? A TFOT result to ASTM D1754 is not an RTFOT result to EN 12607-1, and there is no aged softening point figure on a D946 certificate because that standard does not ask for one. If your specification is European, this has to be arranged at production.

The general rule is the one that applies across this whole site: a grade name belongs to one standard at a time, and a certificate proves only what it was written to prove. Where a cargo has to satisfy a European specification, buy it as EN 12591 40/60 with the EN methods named line by line. Where the project is written in ASTM language, buy a grade ASTM actually defines and accept the property list that comes with it. What is not defensible is treating one system’s certificate as evidence for the other system’s limits, and the ASTM 40-50 page and the grade equivalence reference set out the wider picture, including the Indian viscosity grades. State that comparison carefully, because it fails in a way the penetration arithmetic hides. On penetration alone a 40/60 sits against VG-30, whose IS 73:2013 minimum is 45 dmm, or against VG-40, whose minimum is 35 dmm, depending on where in the band it measures, and it is shut out of VG-20 altogether except at the single value 60, because VG-20 sets a minimum penetration of 60 dmm. But penetration is not what defines an IS 73:2013 grade. Those grades are set by absolute viscosity at 60 °C by IS 1206 Part 2 — 1600 to 2400 poise for VG-20, 2400 to 3600 for VG-30 and 3200 to 4800 for VG-40 — while EN 12591 puts dynamic viscosity at 60 °C by EN 12596 in the group applied according to national circumstances, so it is absent from most European certificates and is measured by a different method when it is present. A 40/60 certificate therefore cannot evidence a VG grade, however the penetration falls, and the only thing that settles it is running the viscosity test itself.

Standard against standard

EN 12591 40/60 compared with ASTM D946 40-50

The two grades sit closer together than any other pair across the two systems, which is exactly why they get confused. This table sets out where they agree, where they differ and where one standard is silent on something the other requires.

EN 12591 grade 40/60 compared with ASTM D946 grade 40-50, the nearest grade the American standard actually names.
Point of comparison Bitumen 40/60 (EN 12591) Bitumen 40-50 (ASTM D946) What it means for the buyer
Governing document EN 12591 ASTM D946 / AASHTO M20, plus refinery export data sheets Two standards with different property lists, not two names for one product
Penetration at 25 °C 40–60 ×0.1 mm, EN 1426 40–50 dmm, ASTM D5 The ASTM band sits wholly inside the EN band, so every compliant 40-50 passes 40/60 on penetration. The reverse fails everywhere above 50, which is the upper half of the European band
Width of the band Twenty units Ten units Two compliant 40/60 cargoes can differ by more than the entire width of the ASTM grade. Where the mix design depends on landing in one part of the band, add a contractual sub-band inside the EN grade
Softening point, ring & ball 48–56 °C required by the standard, EN 1427 No requirement in ASTM D946; export data sheets commonly quote a band, which is practice and not a requirement The most likely gap. A 40-50 cargo has never been obliged to control softening point, so a result outside 48 to 56 °C is a compliant ASTM grade and a failed 40/60
Ageing test RTFOT at 163 °C, EN 12607-1 TFOT at 163 °C for 5 h, ASTM D1754 Different apparatus and film geometry, so different residues. A TFOT result offered against an RTFOT requirement can legitimately be rejected
Ageing limits Change of mass max ± 0.5 %; retained penetration min 50 %; softening point after hardening min 50 °C Retained penetration after TFOT min 55 % for grade 40-50 The two percentages are measured on different residues and do not compare. The EN aged softening point floor has no ASTM counterpart at all, so no D946 certificate can evidence it
Low-temperature requirement Fraass breaking point max -7 °C by EN 12593, where the national annex calls it up No low-temperature requirement of any kind in ASTM D946 The line most often absent when an ASTM-supplied cargo is offered against a European specification, because nobody runs it unless it was ordered
Flash point min 230 °C, EN ISO 2592 min 232 °C, ASTM D92; many export data sheets state min 250 °C One of the few places where the ASTM requirement and the commercial data sheet sit above the European standard, so it rarely causes a rejection
Solubility min 99.0 % in toluene, EN 12592 min 99.0 % in trichloroethylene, ASTM D2042 Same limit, different solvent. A trichloroethylene result is not an EN 12592 result
Ductility Not a requirement of EN 12591 min 100 cm at 25 °C, ASTM D113 A compliant European certificate may legitimately omit it. Ask for it explicitly if your own project document calls it up
Nearest ASTM grade above 60-70, band 60–70 dmm That band touches the 40/60 band at the single value 60, so an ASTM 60-70 at exactly 60 dmm also sits at the very top edge of 40/60. Every caution about band edges applies twice over to a claim resting on one value
Where each is specified Europe, the Balkans, North Africa, the Levant and warm-climate national standards drawn from EN practice The Gulf, South Asia, Southeast Asia and much of sub-Saharan Africa Which grade you are asked for is usually decided by the standard the national road authority adopted, not by the climate at the site
The practical position for a buyer holding a 40/60 specification and an offer of ASTM 40-50 is this. Penetration will pass, because the ASTM band sits wholly inside the European one, subject to the caution about the bottom edge. Flash point and solubility will normally pass on the merits, though the solubility method will be named differently. What is missing is a softening point the producer was never required to control, a Fraass result nobody ordered, and an RTFOT residue in place of a TFOT residue, with an aged softening point floor of 50 °C that has no ASTM equivalent whatsoever. Settle all of that before production, because none of it can be added to a certificate after the cargo has loaded. Working in the other direction, a 40/60 offered against an ASTM 40-50 specification fails outright if its penetration lands above 50, which is the upper half of the European band and includes a great many entirely compliant cargoes.

Applications

Where Bitumen 40/60 is specified

40/60 is a warm-climate general paving grade. It appears where a specification writer has moved one deliberate step up from 50/70 because the summer is hot enough to justify it, and it is one of the standard EN grades in the North African, West African and eastern Mediterranean markets that buy on the European system rather than on ASTM.

1

General highway paving in warm climates

The core application, and the role the EN ladder assigns to this grade. Trunk roads and highways in southern Europe and the Mediterranean basin where summer pavement temperatures make 50/70 marginal but the traffic is not exceptional.

2

Binder and base courses under heavy loading

The intermediate and lower layers that carry the structural work in a thick asphalt pavement. Named in EN 13108 mixture designs where the design traffic makes deformation rather than fatigue the governing distress, and where a full step to 35/50 is not required.

3

North African and West African EN-system markets

Road authorities across the region specify to European standards, so enquiries arrive as EN grade names with EN methods attached. This site publishes market pages for Morocco, Senegal and Cote d’Ivoire.

4

Turkey and the eastern Mediterranean

Markets whose national specifications are drawn from European practice and whose summers put the mainstream grade under pressure. The Turkey supply page covers the route and the documentation, and the markets we serve page lists the rest.

5

Slow and channelised traffic on warm pavements

Junction approaches, bus lanes, climbing lanes and toll plaza aprons, where load duration matters as much as load magnitude. Where the loading is severe as well as slow, the correct step is 35/50 or a modified binder rather than 40/60.

6

Base binder for polymer modification

Where a warm-climate modified binder is produced to EN 14023, a base grade harder than the usual 50/70 is sometimes named. The base grade belongs in the PMB specification in writing rather than being assumed from the finished designation.

The limits

Where Bitumen 40/60 is the wrong choice

A harder binder is not a better binder, and a page that will not name where its product fails is a sales page rather than a reference. Everything 40/60 buys in deformation resistance it pays for in flexibility, fatigue tolerance and workability, and on this grade there is a second category of wrong choice that has nothing to do with climate: the cases where the band is simply too wide for what the job needs.

Genuine cold climates, and anywhere the low-temperature end governs

This is the first and largest exclusion, and it is the one the brief for this grade turns on. EN 12591 sets the Fraass breaking point limit for 40/60 at a maximum of -7 °C, against -8 °C for 50/70, -10 °C for 70/100 and -12 °C for 100/150. Those figures are the standard’s own statement of what each grade is expected to tolerate before a thin film of it cracks when cooled and flexed. A binder qualified to crack at -7 °C is a warm-climate binder. Put it into a pavement that sees hard frosts and the result is low-temperature transverse cracking: regularly spaced cracks across the carriageway, water admitted into the structure, and a defect that cannot be repaired by anything short of resurfacing.

The tell is in the design temperatures rather than the traffic count. Ask what the minimum pavement temperature at the site will be and how far below the Fraass limit it goes. Where the answer is anywhere near -7 °C, move down the ladder to 50/70, 70/100 or softer, or specify against measured low-temperature data rather than against a penetration grade at all. Two further cases belong here even in warm countries: high-altitude routes, where the winter design temperature bears no relation to the coastal climate the rest of the network sees, and continental interiors with cold nights and hot days, where the pavement is asked to survive both ends of the scale at once. In that second case a single unmodified penetration grade is usually the wrong instrument entirely, and the honest answer is a polymer modified binder to EN 14023 or a design carried out against performance grade data, which separates the high-temperature and low-temperature requirements instead of trading one against the other.

Where the twenty-unit band is too wide for the job

This exclusion is specific to 40/60 and it is not about climate at all. The band is twenty penetration units wide, half the value of its own lower edge, and both extremes of it are fully compliant. Where a mix design was closed on a binder at one end of the band and the delivered cargo lands at the other, the plant is working with a materially different material: different viscosity at mixing and compaction temperature, different stiffness in the finished mat, different behaviour in the first hot summer. Three situations make that intolerable rather than merely inconvenient.

  • Repeat supply to one mix design. A plant producing to a fixed recipe across a season needs consistency between cargoes more than it needs any particular point in the band. Buying the grade name alone does not deliver it.
  • Type-tested mixtures. Where a mixture has been type tested under EN 13108 on a specific binder, a compliant cargo from the far end of the band can put the mixture outside the properties it was tested at. The binder is in grade and the mixture is a different mixture.
  • Thin lifts and tight compaction windows. The workable window depends on binder viscosity, and twenty penetration units is enough to change it noticeably. A crew planning around one end of the band and receiving the other will find the difference on the mat rather than on the certificate.

In all three cases the answer is not to abandon the grade but to stop relying on its name. Buy 40/60 to EN 12591 and add a narrower penetration band as an additional contractual limit inside the grade. It costs availability and it will show in price, and both of those are the honest consequences of a tighter requirement.

Thin surfacings, surface dressing and chip seals

Spray-applied and thin-layer work needs a binder that will wet the aggregate, hold the chippings and tolerate the strains a very thin layer sees. 40/60 is too stiff for that duty. It does not wet chippings readily at practical spray temperatures, it gives up chippings under early trafficking, and in a thin layer it has no capacity to absorb strain. Surface dressing and chip sealing are the territory of the softer grades and, in most markets, of bituminous emulsions, and no amount of care with spray rates compensates for starting with the wrong binder.

Emulsion and cutback feedstock

Cationic emulsions classified under EN 13808, and the cutbacks used for prime coats, are normally made from softer base binders, because the residual binder left after the emulsion breaks has to stay flexible in a very thin film. A 40/60 base produces a residue that is stiff, slow to develop adhesion at ambient temperature and unforgiving in tack and prime applications where the film has to wet an existing surface rather than resist a wheel load. Where the job is a prime or tack coat, the grade question is answered by the emulsion specification rather than by choosing a harder paving binder.

Thin pavements and weak or flexible foundations

Deformation resistance is only the governing risk when the structure is thick enough and the foundation stiff enough that rutting is what will actually happen. On a thin asphalt layer over a flexible or marginal foundation, the governing distress is fatigue cracking from repeated bending, and a stiffer binder makes that worse rather than better: it carries more of the bending stress and tolerates less strain before it cracks. Lightly trafficked rural roads, thin overlays on old flexible pavements and surfacing over unbound or weak bases are all cases where a softer, more strain-tolerant binder outlasts a harder one, however counterintuitive that seems. Asphalt mix design basics sets out how the two distress modes trade against each other.

Mixes with a high recycled asphalt content

Reclaimed asphalt brings aged, stiffened binder into the mix, and the blended binder is harder than the virgin binder that went in. Where the recycled content is significant, the usual answer is to select a softer virgin grade so that the blend lands where the design intends. Specifying 40/60 into a high-RAP mix compounds two sources of stiffness and produces a binder nobody designed, with low-temperature and fatigue behaviour nobody has measured. The wide band makes this worse, because the blend outcome depends on where in the twenty units the virgin cargo actually lands.

Where the real problem is heavier than this grade can solve

There is a limit to what one step up the penetration ladder achieves. Where the combination is severe, with very high pavement temperatures, very slow or stationary heavy loads, or a rutting problem that has already appeared on a road built with 50/70, then 40/60 is a half-measure. The honest options are a full step to 35/50 or harder, a high-modulus mix design, or a polymer modified binder certified to EN 14023. A harder unmodified grade improves high-temperature stiffness and degrades everything else; a modified binder is specified precisely because it separates those two outcomes.

Where the specification names a different grade

This one is procedural rather than technical and it is the most common of all. Substituting 40/60 for a specified 50/70 because it sounds stronger, or accepting 50/70 against a 40/60 order because the penetration happens to fall inside your band, is a defect rather than an upgrade or a convenience. The specification writer chose a softening point band and a set of ageing and low-temperature limits, and the neighbouring grade does not deliver all of them. Given how completely these bands overlap, this is the grade where informal substitution is most tempting and most quietly damaging. Any substitution needs the written approval of the engineer who will sign the pavement off, naming the substituted grade and its standard, obtained before shipment rather than after discharge.

Where the destination specification is not European

Two cases. Where the project is written to ASTM D946, 40/60 is not a grade of that standard and there is no limit table for a certificate to prove compliance against; the nearest named ASTM grade is 40-50, and the comparison table above sets out where the two differ and in which direction the containment runs. Where the project is written in performance grades, no penetration grade converts to a PG designation on paper: performance grading requires dynamic shear rheometer and bending beam rheometer results on that specific binder, and two 40/60 cargoes from different crude sources can carry different low-temperature grades. Ask for the test report rather than for a conversion.

The general rule

Choose the softest binder that will resist the deformation the site will actually impose. That sentence is the whole of binder selection for unmodified paving grades. Deformation resistance is bought with stiffness, and stiffness is paid for with cracking resistance, fatigue life and buildability. 40/60 is the right answer when a warm climate and ordinary heavy traffic have made the mainstream grade marginal. Where it is not, a harder grade is a cost with no benefit attached, and it usually presents its bill in the third or fourth winter.

Handling

Working temperatures for Bitumen 40/60

The windows below are common industry practice, not requirements of EN 12591, which sets no handling temperatures at all. They are built by taking this site’s published windows for 35/50 and for 50/70 and spanning them, because that is genuinely what a twenty-unit band demands: a cargo at 42 ×0.1 mm behaves like the harder grade and a cargo at 58 behaves like the softer one. Two documents override every figure here: the project mix design, and the maximum mixture temperature set by the governing EN 13108 product standard and its national annex.

Typical handling temperatures for Bitumen 40/60 as common practice, not as a standard requirement. Defer to the project mix design and the supplier Safety Data Sheet.
Operation Typical range in practice Why it matters
Storage, short term 150–170 °C Hot enough to pump, cool enough that oxidation does not start eating into the retained-penetration and aged-softening-point margins the EN limits depend on. Work in the lower half of the range for a cargo near 60 ×0.1 mm and the upper half for one near 40
Storage, long term below 150–155 °C Prolonged hot storage ages the binder and drops penetration. A cargo received at 42 ×0.1 mm has very little room before it falls below the 40 floor of the grade
Pumping 130–165 °C Viscosity is the constraint and it varies across this band more than across a fifteen-unit one. The bottom of the window is where line pressure, pump wear and cavitation show up first. Lines and valves need to be traced and drained properly
Mixing with aggregate 150–175 °C Where a binder in this band reaches coating viscosity. The EN 13108 product standard and its national annex set the maximum mixture temperature this must stay under, and that ceiling wins over any general table
Aggregate at the mixer 10–15 °C above the target mix temperature Cold aggregate chills the binder film on contact and leaves the fines uncoated. The effect is worse at the hard end of the band because the film stiffens faster
Compaction, start 140–155 °C Density is won or lost here. Rollers belong immediately behind the paver, not at the end of the run
Compaction, cut-off above 90–105 °C Below this the mat is locked in as laid and further rolling only marks the surface. The cut-off arrives earlier for a cargo at the hard end of the band, so plan haul distance and roller pattern around the stiffer case
Absolute maximum do not exceed 180–190 °C With an EN 12591 minimum flash point of 230 °C for this grade, the headroom above this ceiling is narrower than a 250 °C export data sheet implies. Build the safety case on the number printed on your own certificate
Every figure in this table is common industry practice, not a requirement of any standard. EN 12591 specifies the binder, not how it is handled. The ranges are deliberately wider than the ones this site publishes for a single narrower grade, and the reason is the band itself: the 50/70 windows on this site run 150–165 °C for short-term storage, 150–165 °C for mixing and 140–150 °C at the start of compaction, while the 35/50 windows run 155–170 °C, 155–175 °C and 145–155 °C. A 40/60 cargo can sit at either end of that comparison depending on where in its own band it measures, so the practical instruction is to set the schedule from the measured penetration on the Certificate of Analysis rather than from the grade name. Two further points. The workable interval between laying and compaction cut-off is shorter at the hard end of the band, so haul distance, paver speed and roller availability should be planned around the stiffer case rather than adjusted afterwards. And on coils and drum heating: submerge a coil in product before any heat is applied, and never put a flame against a dry drum wall. Localised overheating carbonises binder onto the metal, and the carbonised material then contaminates every batch that passes the same coil afterwards, so the damage outlives the drum it started in and the fire risk is immediate. The heating and temperature guide sets out the practice in more detail and publishes the master table these figures are checked against.

Procurement

Buying Bitumen 40/60, and packing it for export

An EN 12591 purchase has two halves that are easy to confuse: the technical specification the binder must meet, and the paperwork the destination demands. A cargo can satisfy one and fail the other. On this grade there is a third consideration on top, because the overlap with 35/50 and 50/70 makes the grade heading on a certificate less informative than it looks, and the width of the band makes the measured value matter more than usual.

Name the grade, the standard and the methods

The single most effective thing a buyer can do is name the methods rather than only the grade. A purchase order that says Bitumen 40/60 invites a data sheet built around ASTM methods with a European grade name at the top. A purchase order that says Bitumen 40/60 to EN 12591, batch Certificate of Analysis to report penetration by EN 1426, softening point by EN 1427, flash point by EN ISO 2592, solubility in toluene by EN 12592, and the EN 12607-1 RTFOT residue with change of mass, retained penetration by EN 1426 and softening point after hardening by EN 1427, together with the Fraass breaking point by EN 12593 leaves nothing to interpretation. Every item in that sentence is something an engineer at destination will look for, and every one of them has to be arranged before production, because none can be added retrospectively to a cargo that has already loaded.

Require the certificate to be reported against 40/60 specifically

This is the requirement peculiar to this grade and it follows directly from the overlap. Because a batch can satisfy 35/50 and 40/60, or 40/60 and 50/70, at the same time on penetration and softening point, the grade printed at the top of a certificate is not proof that the material was released against your grade’s limit table. Two sentences in the contract close the gap. First, that the Certificate of Analysis shall state the grade as 40/60 to EN 12591 and report every property against the requirements for that grade. Second, that the ageing residue results, meaning retained penetration and softening point after hardening, shall be reported as measured values rather than as pass or fail statements, so that you can check them against the 50 % and 50 °C floors yourself. A certificate that reports only compliance statements cannot be checked against a different grade’s limits, and on this grade that is precisely the check you need to be able to make.

Decide whether you need a sub-band, and say so at enquiry

The twenty-unit band is the second thing to settle before an offer is made rather than after. If your mix design, your plant or your type testing depends on landing in a particular part of the band, write the narrower limit into the enquiry as an additional contractual limit within the EN 12591 40/60 grade, quoting EN 1426 and the range you need. Suppliers can then tell you honestly whether the available material meets it. Asking after the cargo has been produced converts a specification question into a rejection question, and there is nothing in the EN standard to support a rejection of material that is inside the published band.

The inspection scope has to include the slow tests

A standard quality-and-quantity scope from an independent surveyor covers penetration, softening point and the quick lines. A full RTFOT with penetration and softening point run on the residue, and a Fraass determination, are extra laboratory work measured in days rather than hours. If they are not written into the inspection order and into the production plan, they will not appear on the report, and that, rather than any failure of the binder, is the usual reason an otherwise sound EN cargo arrives with an incomplete certificate. Sample drawing should follow a named practice, with sealed retained samples held by both parties. Size the retained quantity for the tests the argument might actually turn on: rechecking penetration and softening point consumes very little material, while re-running an RTFOT and then testing the residue consumes a great deal more. Agree the quantity in the contract rather than discovering at dispute stage that the sealed tin will not stretch to the two tests that matter. On drummed cargo, draw across the whole load instead of from whichever drum sits nearest the container door; the sampling procedure page sets out the practice.

Read the certificate for internal consistency

Penetration and softening point track each other for a straight-run binder of a given crude and process route. A sample reporting 58 ×0.1 mm with a softening point well above 56 °C is not a superior 40/60; it is out of grade, and it suggests material that has been air-blown or blended rather than produced as a straight-run paving bitumen. Reading the two numbers together costs nothing and is the most useful authenticity check available to any penetration-grade buyer. A certificate whose values land exactly on the specification limit batch after batch is a template rather than a test report. The certificate of analysis guide covers what a genuine document looks like, and the fraud prevention page covers the patterns worth recognising before money moves.

CE marking and the Declaration of Performance

Inside the European Union and the EEA, EN 12591 does double duty: it is the technical specification, and it is also the harmonised standard sitting behind CE marking and the Declaration of Performance under the Construction Products framework. That paperwork is generated at the producing plant through initial type testing and factory production control, and it travels with the product. A trading house cannot attach it to a cargo in transit, and it answers a different question from whether the binder meets the numbers in the table above. If your destination sits inside that area, establish before committing tonnage who issues the Declaration of Performance for the material you are buying and what obligations attach to the party whose name appears on the import. The harmonised standards list is revised periodically, so take the position from your importer, your customs broker or the relevant national authority rather than from any supplier’s assurance. Outside that regulatory area the picture is simpler: a great many markets buy to EN 12591 with no CE obligation at all, because the standard is being used purely as a technical specification, and what the engineer wants is a Certificate of Analysis reported against the EN methods.

Packing and container loading

Packing sets container count, the handling plant needed at discharge, waste disposal and how quickly the cargo can be put to work, so it moves landed cost more than most buyers expect. The figures are governed by the packaging rather than by the binder and are the same for any paving grade:

  • New steel drums, 150 kg net: 80 drums in a 20-foot container, about 12 MT per FCL.
  • New steel drums, 180 kg net: 80 drums, about 14.4 MT per 20-foot FCL.
  • New steel drums, 185 kg net: 80 drums, about 14.8 MT per 20-foot FCL.
  • Jumbo or meltable poly bags, 1 MT each: 20 bags, about 20 MT per 20-foot FCL.

One point about those figures is worth stating plainly because it is regularly misread. The 80-drum figure is a floor-pattern limit, not a weight limit. It is how many drums of that diameter stand on the floor of a 20-foot container in a stable pattern, which is why the same 80 drums appear against 150 kg, 180 kg and 185 kg fills and only the tonnage changes. A buyer who assumes the count falls as the fill rises will budget the wrong number of containers. Exact counts still vary with drum dimensions, container type and destination axle weight limits. Where drums are used, write new into the contract, because reconditioned drums are cheaper and are the single most common origin of contamination claims at discharge, and confirm that drum tare is excluded from the invoiced net weight. Jumbo bags suit a buyer with the plant to melt them and leave less packaging waste per tonne to dispose of, while new steel drums suit a site with limited handling equipment. The packaging and logistics and shipping pages set out the options in full, and the tonnage and volume conversions page covers turning invoiced tonnes into tank volume at discharge.

Origin, documents and terms

Material is offered from the Middle East. The commercial file for a shipment is the same as for any bitumen cargo: commercial invoice, packing list, bill of lading, Certificate of Origin from the chamber of commerce, Technical Data Sheet, Safety Data Sheet and the batch Certificate of Analysis, with an independent inspection report where the contract calls for one. The quality control and export documents page sets out what each one is for. Settle the Incoterm before discussing price, because FOB, CFR and CIF put the cost of freight, insurance and risk transfer in different places, and a headline figure quoted on one basis tells you nothing about a figure quoted on another. The Incoterms reference sets out which term carries which obligation. Send quantity, packing, destination port and Incoterm together with the specification you are working to, state plainly whether the full EN test suite is required, and say whether a narrower penetration band inside the grade is part of your requirement, because all three decisions have to be taken before production rather than at the discharge port.

Buyer questions

Frequently asked questions about Bitumen 40/60

What does 40/60 mean in bitumen?

The two numbers are the permitted penetration band, expressed in tenths of a millimetre. Under EN 1426 a needle carrying a 100 g load is released into the conditioned binder at 25 °C for five seconds, and the depth it reaches must land between 40 and 60 for the material to be grade 40/60. EN 1426 is technically equivalent to ASTM D5 and IS 1203; European practice writes the unit as ×0.1 mm where American practice writes dmm, which is the same quantity. Because a lower number means a stiffer binder, 40/60 is harder than 50/70 and softer than 35/50 on the EN 12591 ladder. The grade also carries a softening point band of 48 to 56 °C by EN 1427, which every EN grade has and no ASTM penetration grade does, and a Fraass breaking point limit of -7 °C by EN 12593 where a national annex calls it up.

Why can the same cargo be offered as 35/50, 40/60 or 50/70?

Because the EN 12591 bands overlap on purpose, and around 40/60 the overlap is total. The window 40 to 50 ×0.1 mm belongs to 35/50 and 40/60; the window 50 to 60 belongs to 40/60 and 50/70; and the value 50 belongs to all three. The softening point bands behave the same way: 48 to 54 °C is shared with 50/70 and 50 to 56 °C with 35/50, which together cover the whole 40/60 band. So there is no penetration or softening point result that identifies a binder as a 40/60 and nothing else. Where the three grades separate is on the ageing residue and the low-temperature limit: softening point after hardening must be at least 52 °C for 35/50, 50 °C for 40/60 and 48 °C for 50/70; retained penetration at least 53 %, 50 % and 50 % respectively; and the Fraass breaking point runs the other way at a maximum of -5, -7 and -8 °C. The practical consequence is that the grade name in the contract is a commercial choice as much as a technical one, and a certificate has to be read against the grade you named rather than the grade it is headed with.

Does an ASTM 40-50 certificate satisfy a 40/60 order?

On penetration, yes, and only in that direction. The ASTM D946 40-50 band of 40 to 50 dmm sits entirely inside the EN 40/60 band of 40 to 60, so every compliant 40-50 passes the European penetration requirement. The reverse fails: a 40/60 measuring above 50 is fully compliant in Europe and outside the ASTM band, which is the upper half of the European range. Beyond penetration the answer is no on three separate counts. ASTM D946 sets no softening point requirement for any grade, so a 40-50 cargo has never been obliged to hold 48 to 56 °C and any softening point printed on its data sheet is commercial practice rather than a standard limit. Ageing is assessed by the TFOT of ASTM D1754 rather than the RTFOT of EN 12607-1, which produces a different residue, so the 55 % retained penetration required of ASTM 40-50 and the 50 % required of EN 40/60 are not comparable numbers. And the EN requirement for a softening point of at least 50 °C after hardening has no ASTM counterpart at all, so no D946 certificate can evidence it. One further caution: an ASTM 40-50 released at exactly 40 dmm sits on the floor of the 40/60 band with no margin, and a destination retest reporting 39 puts it outside the grade with neither laboratory being wrong.

What is the difference between 40/60 and 50/70?

One rung on the EN ladder, and the two overlap across a ten-unit window: any binder measuring between 50 and 60 ×0.1 mm satisfies both penetration bands, and any softening point between 48 and 54 °C satisfies both softening point bands. Only two lines separate them. The softening point after hardening on the EN 12607-1 residue must be at least 50 °C for 40/60 against 48 °C for 50/70, and the Fraass breaking point, where a national annex calls it up, is a maximum of -7 °C for 40/60 against -8 °C for 50/70. Retained penetration is 50 % for both and does not separate them at all. On a project, 50/70 is the mainstream European paving grade and 40/60 is the deliberate step up for a climate warm enough that the mainstream grade is being pushed. Because the separation is so narrow, a certificate offered under one heading should always be checked against the limit table of the grade you actually ordered.

What is the difference between 40/60 and 35/50?

35/50 is the harder neighbour, with a penetration band of 35 to 50 and a softening point band of 50 to 58 °C. The two share the window 40 to 50 on penetration and 50 to 56 °C on softening point, so a great many batches satisfy both. Three lines separate them. 35/50 requires retained penetration after RTFOT of at least 53 % against 50 % for 40/60, and a softening point after hardening of at least 52 °C against 50 °C. The Fraass breaking point runs the other way: 40/60 carries the more demanding maximum of -7 °C against -5 °C for 35/50, so neither grade is simply stricter than the other. Their roles differ too. 35/50 is specified where heavy, slow or channelised traffic on a warm pavement makes rutting the governing risk and the layer must also serve as a running surface, while 40/60 is general highway paving in warm climates.

What ageing requirements does EN 12591 set for 40/60?

Ageing is assessed by the rolling thin-film oven test to EN 12607-1, which ages a continuously renewed film of binder in rotating glass bottles with an air jet at 163 °C. EN 12591 then places three limits on the residue for this grade: change of mass no more than ± 0.5 % by weight, retained penetration at least 50 % of the original value, and softening point after hardening at least 50 °C. Note the plus-or-minus on the mass line, because a binder can gain mass through oxidation as well as lose it through volatilisation, so a certificate reporting only a loss figure has answered half the question. Put numbers on the retained penetration line: a cargo entering the test at 52 ×0.1 mm must still measure at least 26 afterwards. The aged softening point is the most useful line on a 40/60 certificate, because it is the only EN 12591 requirement whose value is different for 35/50, 40/60 and 50/70, which makes it the one line that can tell those three grades apart. A thin-film oven test result to ASTM D1754 is a different test on a different film geometry and is not a substitute.

When is 40/60 the wrong grade to specify?

In more situations than its position in the middle of the ladder suggests. It is wrong wherever the low-temperature end governs: its Fraass breaking point limit of -7 °C is a warm-climate limit, against -8 °C for 50/70, -10 °C for 70/100 and -12 °C for 100/150, and the failure mode is low-temperature transverse cracking that cannot be repaired short of resurfacing. High-altitude routes and continental interiors with cold nights and hot days belong in the same category, and in the second case an unmodified penetration grade is usually the wrong instrument altogether. It is wrong for surface dressing, chip seals and thin surfacings, which need a binder that wets and holds chippings; wrong as emulsion or cutback feedstock, where softer base binders are used; wrong for thin layers over weak or flexible foundations, where fatigue rather than rutting governs; and wrong in high-RAP mixes, where the aged recycled binder already stiffens the blend. It is also the wrong answer where the loading is severe enough that a full step to 35/50, a high-modulus mix or a polymer modified binder to EN 14023 is what the situation actually calls for. One exclusion is specific to this grade: where a mix design or a type-tested mixture depends on a consistent binder, a twenty-unit band is too wide to buy by name alone, and the fix is a narrower contractual penetration band inside the EN grade.

What must the Certificate of Analysis show, and does CE marking apply?

For an EN 12591 order the certificate should carry measured, batch-specific values with the EN method printed against each line: penetration by EN 1426, softening point by EN 1427, flash point by EN ISO 2592, solubility in toluene by EN 12592, and the EN 12607-1 residue reported as change of mass, retained penetration and softening point after hardening, plus a Fraass breaking point by EN 12593 where the destination calls it up. Ask for the ageing lines as measured numbers rather than pass-or-fail statements, so that you can check them against the 50 % and 50 °C floors for 40/60 yourself. That check matters on this grade in particular, because the same batch can satisfy 35/50 or 50/70 as well and the grade heading alone does not tell you which limit table the material was released against. On CE marking, the answer depends on the destination rather than on the grade. Inside the European Union and the EEA, paving grade bitumen is placed on the market under the Construction Products framework with a Declaration of Performance issued by the producing plant; confirm the current position with your importer or the national authority, since the harmonised standards list is revised periodically. In the many markets outside that area that use EN 12591 purely as a technical standard, no CE marking is involved.

QC
How this page is maintainedThe requirement values on this page are attributed to EN 12591 and each is tied to the European test method that produces it (EN 1426, EN 1427, EN 12592, EN 12593, EN 12595, EN 12596, EN 12607-1, EN 15326 and EN ISO 2592), with the ASTM counterpart named where one exists. The penetration and softening point bands quoted for 35/50, 40/60, 50/70 and every other grade on the ladder are the bands this site publishes across its EN 12591 references, and the overlap arithmetic that runs through this page is derived from them rather than asserted. Those bands, including the 30 to 38 °C softening point band shown for EN 12591 grade 250/330, are stated on the authority of that reference rather than independently verified here against the standard text, so the ladder table is attributed on that basis and the contractual limit for any grade on it must be taken from the edition of EN 12591 the contract cites together with any applicable national annex. Where EN 12591 applies a requirement according to national circumstances and climate, which covers the Fraass breaking point, the maximum increase in softening point after hardening, kinematic viscosity by EN 12595, dynamic viscosity by EN 12596 and wax content by EN 12606-1, that is stated explicitly, and limits that are grade-specific and not reproduced here should be taken from the current edition and the applicable national annex. Handling temperatures are described as common industry practice, not as requirements of any standard; they are built by spanning the windows this site already publishes for 35/50 and 50/70, and they remain subordinate to the project mix design, the maximum mixture temperature set by the governing EN 13108 product standard, and the supplier Safety Data Sheet. Comparative ASTM D946 figures are attributed to that standard, and figures that are refinery or trading practice on export data sheets, including softening point ranges quoted for ASTM paving grades, are labelled as practice rather than as requirement. Nothing here is a contractual guarantee: the binding specification for any shipment is the one agreed in the sales contract and evidenced by the batch Certificate of Analysis. Standards are revised, so verify any limit against the current edition of EN 12591 before it goes into a contract, and if a value on this page conflicts with that edition, tell us and it will be corrected.

Request a Bitumen 40/60 quotation

Send quantity, packing, destination port and Incoterm, together with the specification you are working to. State whether the cargo must be certified against EN 12591, including the RTFOT residue results by EN 12607-1 and, where your national annex calls it up, the Fraass breaking point by EN 12593, because those have to be arranged before production rather than added to a Certificate of Analysis afterwards. If your mix design needs a narrower penetration range than the full 40 to 60 band, say so in the enquiry and the offer will state plainly what the available material can actually be certified to. If your specification could equally be served by 35/50 or 50/70, say that too.

Send RFQ on WhatsApp

WA

Email enquiry WhatsApp enquiry